| Permit Number |
00120912 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-01-23 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | ALL COMMENTS FROM REVIEW DATED 12/03/01 | | | NOT ADDRESSED. | | | | | | 1) SHT C-3, DRINKING FOUNTAIN DETAIL, | | | SHT L-5 DETAIL I. HI/LOW DRINKING FOUNT- | | | AIN REQUIRED FOR HDCP SEC 4.15 AND FOR | | | THOSE WHO HAVE TROUBLE BENDING OR STOOP- | | | ING SEC 4.1.3(10). | | | 2) SHT A8.0, DETAIL 3/A8.0. SINKS TO | | | COMPLY WITH FACBC SEC 4.24. PLEASE SHOW | | | DETAILS OF ALL SUBSECTIONS OF THIS SEC. | | | 3) SHTS P1.0 & P2.0, FUNNEL FLOOR DRAIN | | | NOT APPROVED. FLOOR SINK WITH TRAP PRIM- | | | ER REQUIRED FOR ALL INDIRECT WASTE. SPC | | | SEC 804.5 | | | 4) SHTS P1.0 & P2.0, PLUMBING FIXTURE | | | SECHEDULE, PAN DRAIN & P/T TO DISCHARGE | | | TO OUTDOORS. WATER HEATER DETAIL SHOWS D | | | RAIN TO FLOOR DRAIN. PLEASE CLAIRFY. | | | 5) SHT P2.0, HVAC CONDENSATE RISER, RE | | | LIEF VENT REQUIRED TO 6" ABOVE GRADE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|