| Plan Review Notes For Permit 00120912 |
| Permit Number |
00120912 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-12-17 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 00120912 | | | 116 21 ST ST | | | COLEMAN PARK | | | CONT: JMW CONSTRUCTION CORP | | | (561) 417-0077 | | | | | | 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING | | | (2 COPIES) OF EITHER SBCCI OR DADE COUN- | | | TY PRODUCT APPROVALS REQUIRED FOR ALL | | | GLAZED OPENINGS.LARGE MISSLE IMPACT | | | RESISTANCE TESTING REQUIRED. | | | CITY SPEC: | | | 08112.1(102) SUBMITTALS, DOORS | | | 082212.2.2(D/E) SUBMITTALS, SLIDING | | | GLASS DOORS | | | 08800.3(102C) SUBMITTALS, WINDOWS | | | IF GLAZED OPENINGS ARE NOT BE PART OF | | | THIS PERMIT WE SHALL REQUIRE A LETTER | | | FROM THE CONTRACTOR REQUESTING THIS. | | | A SEPERATE PERMITE FOR GLAZED OPENINGS | | | THEN WOULD BE PROVISOED WITH SEPERATE | | | APPLICATION ,REQUIREMENTS & FEES. | | | | | | DETAIL 7A/7.0 INDICATES 3/4" PLYWOOD | | | ROOF SHEATHING, VS SHEET S-3 INDICATES | | | 5/8" PLYWOOD. CORRECT DISCREPANCY. | | | | | | CONTRACTOR IS TO HAVE THE COUNTY ASSESS | | | PLANS FOR COUNTY IMPACT FEES.PLANS ARE | | | TO BE STAMPED & A COPY OF FEE RECEIPT | | | SUBMITTED TO CITY. | | | | | | PAY STATE TRAINING FEES TO CITY @ .01/ | | | SQ FT.#38.00. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|