Plan Review Notes
Plan Review Notes For Permit 00120912
Permit Number 00120912
Review Stop P
Sequence Number 3
Notes
Date Text
2001-12-03 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT C-3, DRINKING FOUNTAIN DETAIL,
 SHT L-5 DETAIL I. HI/LOW DRINKING FOUNT-
 AIN REQUIRED FOR HDCP SEC 4.15 AND FOR
 THOSE WHO HAVE TROUBLE BENDING OR STOOP-
 ING SEC 4.1.3(10).
 2) SHT A8.0, DETAIL 3/A8.0. SINKS TO
 COMPLY WITH FACBC SEC 4.24. PLEASE SHOW
 DETAILS FOR ALL SUBSECTIONS OF THIS SEC.
 3) SHTS P1.0 & P2.O, FUNNEL FLOOR DRAIN
 NOT APPROVED. FLOOR SINK WITH TRAP PRIM-
 ER REQUIRED FOR ALL INDIRECT WASTE. SPC
 SEC 804.5
 4) SHTS P1.0 & P2.0, PLUMBING FIXTURE
 SCHEDULE, PAN DRAIN & P-T TO DISCHARGE
 TO OUTDOORS. WATER HEATER DETAIL SHOWS
 DRAIN TO FLOOR DRAIN. PLEASE CLAIRFY.
 5) SHT P2.O, HVAC CONDENSATE RISER, RE-
 LIEF VENT REQUIRED TO 6" ABOVE GRADE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377