| Plan Review Notes For Permit 00120912 |
| Permit Number |
00120912 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-12-05 00:00:00 | | | | PROVISO: | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS (NFPA 90A | | | 4-4.4.3). | | | | | | EMERGENCY DRAIN PAN SHALL HAVE OVERFLOW | | | PROTECTION BY MEANS OF AN APPROVED FLOAT | | | SWITCH OR A DRAIN TO A CONSPICUOUS | | | POINT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|