| Plan Review Notes For Permit 00120912 |
| Permit Number |
00120912 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-29 00:00:00 | 1) THE CHAIN-LINK FENCE AROUND THE | | | BACKFLOW DEVICE IS NOT TO OBSTRUCT OR | | | INTERFERE WITH ACCESS OR USE TO THE | | | FIRE DEPARTMENT CONNECTION. | | | 2) THE FIRE LINE BACKFLOW DEVICE IS | | | TO BE EQUIPPED WITH TAMPER SWITCHES, | | | AND A CHAIN AND LOCK. | | | 3) FIRE SPRINKLER HEADS 103 AND 104 MUST | | | BE AT LEAST SIX FEET APART TO PREVENT | | | COLD SOLDERING FROM TAKING PLACE. | | | 4) ANY ROOM WHICH HAS AN OCCUPANT LOAD | | | OF 50 OR MORE PERSONS, DOOR(S) MUST | | | SWING IN THE DIRECTION OF EXIT TRAVEL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|