2001-05-02 00:00:00BUILDING PLAN REVIEW
 PLAN CHECK III
 COLEMAN PARK
 1116 21ST STREET
 PERMIT # 00120912
  
 1)- SBC 104.2.2. A DETAIL WILL BE
 REQUIRED FOR THE WINDOW BUCK ATTACHMENT.
 DETAILING WHAT TYPE OF ANCHOR IS TO BE
 USED AND THE SPACING.
  
 2)- SBC 1606.2.6.2. COMPONENTS &CLADDING
 PRODUCT APPROVAL REPORTS WILL BE RE-
 QUIRED FOR ALL GLAZED OPENINGS INCLUDING
 WINDOWS & DOORS. THESE PRODUCT APPROVAL
 REPORTS CAN BE A PROVISO THAT THE CON-
 TRACTOR BRING THE REPORTS IN BEFORE THE
 FRAMING INSPECTION. THE CITY ACCEPTS
 S.B.C.C.I. REPORTS AS WELL AS DADE COUN-
 TY PRODUCT APPROVAL. IT MUST BE NOTED IF
 THE GLAZED OPENINGS HAVEN'T PASSED LARGE
 MISSLE IMPACT RESISTANCE TESTING THEN
 STORM SHUTTERS WILL BE REQUIRED. A SEPER
 ATE PERMIT WITH FEES WILL BE REQUIRED AS
 CITY POLICY.
  
 3)-SBC 1505.3.2/ 1505.4.1.2. ROOFING
 MATERIALS WILL REQUIRE PRODUCT TESTING
 FOR 110 MPH.
  
 4)- DETAIL 7A/7.0 SHOWS 3/4 " PLYWOOD
 ROOF SHEATHING VS. SHEET S-3 INDICATES
 5/8 " PLYWOOD.
  
 5)- THE INTERIOR LOBBY SHOWS A GWB
 CEILING ATTACHED TO METAL STUD FRAMING,
 THERE IS NO DETAIL SHOWING SPACING OF
 FRAMING OR SIZE OF FRAMING.
  
 BUILDING PLAN REVIEW.