| Plan Review Notes For Permit 00120912 |
| Permit Number |
00120912 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-05-02 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK III | | | COLEMAN PARK | | | 1116 21ST STREET | | | PERMIT # 00120912 | | | | | | 1)- SBC 104.2.2. A DETAIL WILL BE | | | REQUIRED FOR THE WINDOW BUCK ATTACHMENT. | | | DETAILING WHAT TYPE OF ANCHOR IS TO BE | | | USED AND THE SPACING. | | | | | | 2)- SBC 1606.2.6.2. COMPONENTS &CLADDING | | | PRODUCT APPROVAL REPORTS WILL BE RE- | | | QUIRED FOR ALL GLAZED OPENINGS INCLUDING | | | WINDOWS & DOORS. THESE PRODUCT APPROVAL | | | REPORTS CAN BE A PROVISO THAT THE CON- | | | TRACTOR BRING THE REPORTS IN BEFORE THE | | | FRAMING INSPECTION. THE CITY ACCEPTS | | | S.B.C.C.I. REPORTS AS WELL AS DADE COUN- | | | TY PRODUCT APPROVAL. IT MUST BE NOTED IF | | | THE GLAZED OPENINGS HAVEN'T PASSED LARGE | | | MISSLE IMPACT RESISTANCE TESTING THEN | | | STORM SHUTTERS WILL BE REQUIRED. A SEPER | | | ATE PERMIT WITH FEES WILL BE REQUIRED AS | | | CITY POLICY. | | | | | | 3)-SBC 1505.3.2/ 1505.4.1.2. ROOFING | | | MATERIALS WILL REQUIRE PRODUCT TESTING | | | FOR 110 MPH. | | | | | | 4)- DETAIL 7A/7.0 SHOWS 3/4 " PLYWOOD | | | ROOF SHEATHING VS. SHEET S-3 INDICATES | | | 5/8 " PLYWOOD. | | | | | | 5)- THE INTERIOR LOBBY SHOWS A GWB | | | CEILING ATTACHED TO METAL STUD FRAMING, | | | THERE IS NO DETAIL SHOWING SPACING OF | | | FRAMING OR SIZE OF FRAMING. | | | | | | BUILDING PLAN REVIEW. | | | JIM WITMER | | | (561) 659- 8096 EX 8412 |
|