| Plan Review Notes For Permit 00120912 |
| Permit Number |
00120912 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-09 00:00:00 | DENIED; | | | | | | 1.PAGE R-1 SHOW RAIN SENSOR LOCATION. | | | | | | 2.PAGE P2.0 WATER HEATER DETAIL. PAN | | | DRAIN TO BE 1" 94 SPC 507.8.2. | | | | | | 3.RELIEF LINE TO BE PIPED SEPARATELY TO | | | TERMINATION POINT SPC507.8.4. | | | | | | 4.SANITARY RISER DIAGRAM.FLOOR DRAINS IN | | | PUBLIC BATHROOMS MUST BE 3" SPC | | | 409.4.1.1. | | | | | | 5.AIR CHAMBERS TO CAMPLY WITH 607.8.2. | | | | | | 6.PLUMBING FIXTURE SCHEDULE SHOWS FLUSH | | | VALVES. WATER RISERSHOWS 1/2" WATER TO | | | W/C FLUSH VALVES ARE MIM.3/4". | | | | | | 7.TWO FIXTURES ON COLD WATER ONLY. | | | COUNTY AMENDMENTS.97EDITION. | | | | | | 8.SHOW SQUIRE FOOTAGE CALCULATIONS AND | | | FIXTURE REQUIRED FOR MIMIMUM | | | FACILITIES. COMPLY TO TABLE 407 OF | | | 94 PLUMBING CODE. | | | | | | 9.SIZE HORIZONTAL AND VERTICAL RAIN | | | LEADERS USING TABLE 1108.1 AND 1108.2 | | | | | | 10.SHOW CONDENSATE PIPING. SIZE AND | | | DESTINATION. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|