2001-01-09 00:00:00DENIED;
  
 1.PAGE R-1 SHOW RAIN SENSOR LOCATION.
  
 2.PAGE P2.0 WATER HEATER DETAIL. PAN
 DRAIN TO BE 1" 94 SPC 507.8.2.
  
 3.RELIEF LINE TO BE PIPED SEPARATELY TO
 TERMINATION POINT SPC507.8.4.
  
 4.SANITARY RISER DIAGRAM.FLOOR DRAINS IN
 PUBLIC BATHROOMS MUST BE 3" SPC
 409.4.1.1.
  
 5.AIR CHAMBERS TO CAMPLY WITH 607.8.2.
  
 6.PLUMBING FIXTURE SCHEDULE SHOWS FLUSH
 VALVES. WATER RISERSHOWS 1/2" WATER TO
 W/C FLUSH VALVES ARE MIM.3/4".
  
 7.TWO FIXTURES ON COLD WATER ONLY.
 COUNTY AMENDMENTS.97EDITION.
  
 8.SHOW SQUIRE FOOTAGE CALCULATIONS AND
 FIXTURE REQUIRED FOR MIMIMUM
 FACILITIES. COMPLY TO TABLE 407 OF
 94 PLUMBING CODE.
  
 9.SIZE HORIZONTAL AND VERTICAL RAIN
 LEADERS USING TABLE 1108.1 AND 1108.2
  
 10.SHOW CONDENSATE PIPING. SIZE AND
 DESTINATION.
  
 PLUMBING PLAN REVIEW BY;