Plan Review Notes
Plan Review Notes For Permit 00120912
Permit Number 00120912
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 REQUIRED PER CITY CODE REQUIREMENTS.
 2) THE REGULATORY AREA OF THE PLANS
 INDICATES THAT THE BUILDING WILL NOT
 BE FIRE SPRINKLER PROTECTED. NOTED IN
 THE PLANS WAS PAGE SP1.1 WHICH INDICATED
 FIRE SPRINKLER PROTECTION. PLEASE
 CORRECT DISCREPANCY. IF FIRE SPRINKLER
 ARE TO BE PROVIDED, THEN HYDRAULIC
 CALCULATIONS ARE TO BE PROVIDED WITH
 PLANS.
 3) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM SHOP DRAWINGS FOR FIRE ALARM
 EQUIPMENT SHOWN ON DRAWINGS.CUT SHEETS
 ON DEVICES PLANNED FOR USE ARE REQUIRED.
 ADDITIONAL FIRE ALARM DEVICES APPEAR
 TO BE NEEDED.
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS.
 5) PLEASE PROVIDE MORE DETAILS ON KILN.
 6) DESCRIBE PURPOSE OF MEZZANINE.
 7) PLEASE INDICATE CONSTRUCTION OF
 COVERED WALKWAY. IF COMBUSTIBLE AND OVER
 FOUR FEET WIDE, FIRE SPRINKLERS WILL
 BE REQUIRED.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910