| Plan Review Notes For Permit 00120912 |
| Permit Number |
00120912 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE SHEET E2-0, CIRCUIT | | | A-19. PLEASE SHOW AS GFI OR IDENTIFIY | | | ON PANEL SCHEDULE AS GFI PROTECTED PER | | | 210-8. | | | | | | 2)NOTE: PLEASE PROVIDE INFORMATION ON | | | AIC RATING OF MAIN DISCONNECT PER 110-9. | | | | | | 3)NOTE:PLEASE NOTE PER 250-50 COLD | | | WATER BOND TO GROUNDING ELECTRODE SYSTEM | | | | | | 4)NOTE: PLANS SIGNED AND SEALED | | | PER FAC. 61G15-23.002 AND 471.25 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PLAMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|