2001-01-08 00:00:00BUILDING REVIEW:
 1)- FL ACCESSIBILITY CODE 4.6.3 ACCESS
 AISLE SHALL BE DIAGONALLY STRIPED.
 2)- FL ACCESSIBILITY CODE 4.6.6 ACCESS
 AISLES SHALL BE 5'X20' LEVEL WITH A
 SURFACE SLOPE NOT EXCEEDING 1:50 OR 2%
 IN ANY DIRECTION.
 3)- FL STATE STATUTE 481 PLANS ARE TO
 BESIGNED, SSEALED & DATED.
 4).SBC 1804.2 SOILS TEST REPORT
 REQUIRED.
 5)- 400.3ABCD.1.(2) ENERGY CALCULATIONS
 SIGNED BY THE PERSON PREPARING THE COM-
 PLIANCE CALCULATION AS A TRUE & ACCURATE
 AND DEMONSTRATES THAT THE BUILDING IS IN
 COMPLIANCE.
 6)- SBC 104.2.2 WINDOW BUCK ATTACHMENT
 ADDITIONAL INFORMATION REQUIRED, DETAIL.
 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 WILL REQUIRE PRODUCT APPROVAL REPORTS
 FOR ALL WINDOWS,EXTERIOR DOORS & ROOFING
 MATERIALS.
 8)- WF-16 NOT IN FOOTING SCHEDULE SEE
 S-1 DRAWINGS.
 9)- W8X21- NOT IN FOOTING SCHEDULE.
 10)- SBC 103.7.1- ALTERNATE METHODS, IN-
 ITIAL CHEMICAL SOIL TREATMENT IN SIDE
 FOUNDATION WALLS (BLOCK CELLS) SHALL
 OCCUR AFTER ALL EXCAVATION, BACK FILLING
 & COMPACTION.NOTE 103.7.1.3 CELLS & CAV-
 ITIES IN MASONARY WALLS SHALL BE CLEANED
 OF ALL TRASH / DEBRIS, WOOD SCRAPS OR
 OTHER EXTANEOUS CONTENT BEFORE TTERMITE
 TREATMENT.
 11)- SBC 103.7.3.5- ADDITIONAL CHEMICAL
 TREATMENT SHALL BE APPLIED UNDER ALL
 EXTERIOR CONCRETE ON GRADE WITHIN 1 FT.
 OF THE PRIMARY STRUCTURE WALLS.
 12)-SBC 104.2.2- 2'X2' MASONARY COLUMNS
 ARE NOT ON THE COLUMN SCHEDULE, STEEL
 SIZE? A7.05 SHOWS ALL CELLS FILLED?
 13)-104.2.2- S-2 MEZANINE ADD. INFO.REQ.
 AT TB-2 THE #4@8" O.C. 8'-6" LONG' IS
 THERE ANY BOTTOM STEEL?
 14)-STORAGE/ JAN. RM.- ON THE WEST SIDE
 OF THE OPENING IS THERE BOTTOM STEEL
 REQUIRED IN THE MEZANINE SLAB OR TEMPER-
 ATURE BARS?
 15)- TRUSS PLAN LAYOUT W/ DESIGN LOAD
 INFORMATION FOR SBC 1606.1 OR ASCE 7-95.
 WIND LOAD CONSISTANT WITH THE DESIGNER
 OF RECORD ASSUMPTIONS.
 16)- DISCREPANCY- HIGH ROOF FRAMING PLAN
 SHOWS A DROPPED RAKE BEAM. THE PLANS
 SHOW A 2"X6"@3'-0" VS. DETAIL#5 INDICATE
 THAT 2"X8"@ 4'-0" O.C. WILL BE USED?ALSO
 CHECK THE MAX SPAN TABLES FOR 5/8"
 PLYWOOD.
 17)- DETAILS 7/A7.0 SHOWS 3/4" PLYWOOD
 ROOF SHEATHING VS. SHEET S.3 INDICATES
 5/8" PLYWOOD.
 18)- THE INTERIOR OF THE LOBBY SHOWS A
 GWB CEILING OVER METAL STUD FRAMING,
 THERE IS NO DETAIL SHOWING HOW THECEIL
 ING IS TO BE FASTENED TO THE 3X12 & 4X12
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412