| Plan Review Notes For Permit 00120903 |
| Permit Number |
00120903 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | | | | 1.RISER DIAGRAM NOT TO CODE. SPC 914. | | | CIRCUIT OR LOOP VENTING SHOULD BE USED | | | FOR NEW PLUMBING. URINAL SHOULD HAVE | | | ITS OWN VENT. | | | | | | 2.SHOW A WATER RISER DIAGRAM. | | | | | | 3.SHOW SQUIRE FOOTAGE CALCULATIONS AND | | | FIXTURES REQUIRED TO COMPLY WITH SPC | | | TABLE 407. SEE 407.1.3 FOR SQUIRE | | | FOOTAGE YOU CAN DEDUCT. | | | | | | 4.DRINKING FOUNTAINS ARE REQUIRED TO | | | COMPLY WITH FACBC SECS. 4.1.3(10) AND | | | 4.15. PROVISIONS SHALL BE MADE FOR | | | PEOPLE WHO HAVE TROUBLE BENDING OR | | | STOOPING. | | | | | | 5.LOUNGE SINK MUST COMPLY WITH FACBC | | | 4.24.1 THRU 4.24.7. SHOW ELEVATION | | | DRAWINGS. | | | | | | 6.WALLS AND FLOORS OF PUBLIC RESTROOMS | | | SHALL BE LINED WITH NONABSORBENT | | | MATERIAL TO A HEIGHT OF 4' ABOVE FLOOR | | | SBC 1204.2. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT;8377 |
|