2001-01-08 00:00:00DENIED;
  
 1.RISER DIAGRAM NOT TO CODE. SPC 914.
 CIRCUIT OR LOOP VENTING SHOULD BE USED
 FOR NEW PLUMBING. URINAL SHOULD HAVE
 ITS OWN VENT.
  
 2.SHOW A WATER RISER DIAGRAM.
  
 3.SHOW SQUIRE FOOTAGE CALCULATIONS AND
 FIXTURES REQUIRED TO COMPLY WITH SPC
 TABLE 407. SEE 407.1.3 FOR SQUIRE
 FOOTAGE YOU CAN DEDUCT.
  
 4.DRINKING FOUNTAINS ARE REQUIRED TO
 COMPLY WITH FACBC SECS. 4.1.3(10) AND
 4.15. PROVISIONS SHALL BE MADE FOR
 PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING.
  
 5.LOUNGE SINK MUST COMPLY WITH FACBC
 4.24.1 THRU 4.24.7. SHOW ELEVATION
 DRAWINGS.
  
 6.WALLS AND FLOORS OF PUBLIC RESTROOMS
 SHALL BE LINED WITH NONABSORBENT
 MATERIAL TO A HEIGHT OF 4' ABOVE FLOOR
 SBC 1204.2.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT;8377