| Notes |
| Date |
Text |
| 2001-01-19 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE AO, PROVIDE ELEVATION CERT. | | | 2-REVISE ENERGY CALCULATIONS ADDRESS AND | | | COMPLETELY FILL BOTTOM OF FORM. | | | 3-PROVIDE SOIL TEST REPORT AS PER SECT. | | | 1804.2.7.2 AND TABLE 1804.2.7.3 OF | | | CITY AMENDMENTS TO SBC 1997. | | | 4-PROVIDE COMPLETE STORM PANELS INFO. | | | UNDER A SEPARATE PERMIT. | | | 5-PROVIDE PRODUCT APPROVAL FOR: | | | -INSWING ENTRY DOORS. | | | -BBQ UL LISTING AND SPECIFICATIONS. | | | -FRENCH DOORS AS SHOWN ON THE OPTIONS. | | | 6-PROVIDE MANUFACTURER'S CERTIFICATION | | | THAT CONCRETE BLOCK EQUIVALENT | | | THICKNESS WILL PROVIDE TWO HOUR FIRE | | | RATING ACCORDING TO ASTM C140. | | | SECTION 709.3 SBC 1997. | | | 7-CLARIFY/REVISE DOOR BUCK DETAIL. BUCK | | | SIZE IS 2X4 AND ANCHOR IS 1 1/2" LONG. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT 659-8096 EXT. 8232. |
|