| 2001-02-06 00:00:00 | ***************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRNET PER 110-9. |
| | PLEASE SEE NOTE#16 FROM FIRST REVIEW. |
| | A NOTE WAS ADDED TO E-1 FOR A/C |
| | EQUIPMENT RATING? 110-9 OF NEC IS FOR |
| | AIC RATING |
| | |
| | |
| | 2)NOTE: PLEASE SHOW LOCATION OF EXISTING |
| | SERVICE, YOU SHOW MAIN DISCONNECT ON |
| | GARAGE, AND NOT GROUPED WITH MAIN FROM |
| | HOUSE PER 230-72 |
| | |
| | 3)NOTE: PLEASE NOTE FROM FIRST NOTES, |
| | YOU SHOW AN EQUIPMENT GROUNDING |
| | CONDUCTOR FROM METER TO FIRST MEANS OF |
| | DISCONNECT.EQUIPMENT GROUNDING COND |
| | ONLY AFTER FIRST MEANS OF DISC. |
| | |
| | 4)NOTE: PLEASE NOTE THAT PANEL "A"/"B" |
| | "SCHEDULES BOTH SHOW MCB`S W MAIN |
| | DISCONNECT INLINE. PLEASE VERIFY. |
| | |
| | 5)NOTE: PLEASE NOTE LOAD ON GARAGE |
| | PANELSHOWN WITH NO ROOM FOR SPARES PER. |
| | YOU ARE SHOWING # 6 COMING FROM METER |
| | WITHNO MEANS OF OCP.? PLEASE CORRECT. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION. IF |
| | THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 659-8096 EXT 8372 |