2001-02-06 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
 PLEASE SEE NOTE#16 FROM FIRST REVIEW.
 A NOTE WAS ADDED TO E-1 FOR A/C
 EQUIPMENT RATING? 110-9 OF NEC IS FOR
 AIC RATING
  
  
 2)NOTE: PLEASE SHOW LOCATION OF EXISTING
 SERVICE, YOU SHOW MAIN DISCONNECT ON
 GARAGE, AND NOT GROUPED WITH MAIN FROM
 HOUSE PER 230-72
  
 3)NOTE: PLEASE NOTE FROM FIRST NOTES,
 YOU SHOW AN EQUIPMENT GROUNDING
 CONDUCTOR FROM METER TO FIRST MEANS OF
 DISCONNECT.EQUIPMENT GROUNDING COND
 ONLY AFTER FIRST MEANS OF DISC.
  
 4)NOTE: PLEASE NOTE THAT PANEL "A"/"B"
 "SCHEDULES BOTH SHOW MCB`S W MAIN
 DISCONNECT INLINE. PLEASE VERIFY.
  
 5)NOTE: PLEASE NOTE LOAD ON GARAGE
 PANELSHOWN WITH NO ROOM FOR SPARES PER.
 YOU ARE SHOWING # 6 COMING FROM METER
 WITHNO MEANS OF OCP.? PLEASE CORRECT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION. IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372