Plan Review Notes
Plan Review Notes For Permit 00120708
Permit Number 00120708
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PLANS THAT CORRE-
 -LATE WITH WORK BEING DONE.
 PANEL SCHEDULE SUBMITTED SHOWS GARAGE
 DOORS?? PANEL"B" IS SHOWN ON RISER FOR
 GARAGE???
 ALSO PANEL "B" IS SHOWN ON PLAN FOR
 GARAGE BUT WHERE IS MAIN DISC THAT IS
 SHOWN ON RISER???
 ALSO PLEASE SUBMIT PANEL "B" PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE SHOWING ALL GROUNDING AT
 GARAGE, CWP/BLDG STEEL. PER 250-50
 PLEASE NOTE MISSING EQUIPMENT GROUND
 FROM MAIN HOUSE IN CONDUIT.
 PLEASE SHOW SERVICE LOCATION ON PLAN.
  
 3)NOTE: MISSING SMOKE DETECTOR ON LOWER
 LEVEL PER NFPA-72 2-2.1.1.1 MAIN HOUSE.
  
 4)NOTE: PLEASE NOTE MEANS OF EGRESS
 LIGHTING REQ`D IN GARAGE GOING UP TO
 STORAGE AREA. STAIR LIGHITNG?? 210-70
  
 5)NOTE: EXISTING ELECTRICAL RISER SHOWS
 SHOWS GARAGE DISCONNECT AND PANEL COMING
 FORM MAIN DISCONNECT?? THESE ARE SHOWN
 AS TAPPED CONDUCTORS? WHERE IS OCP FOR
 THIS.PNAEL"A" DOES NOT SHOWN FEEDING "B?
  
 6)NOTE: 2/0 CONDUCTORS ARE SHOWN FEEDING
 A 2P50A?? PLEASE SHOW CLARIFICATION
 ON HOW 2/0`S WILL GO INTO 50A 2P.??
  
 7)NOTE: PLEASE SUBMIT REVISED LOAD CAL-
 -CULATIONS TO INCLUDE ALL NEW LOADS
 IN GARAGE.....A/C ECT.
  
 8)NOTE: SPRINLLER AT GARAGE?? PUMP?
 PLEASE SHOW ALSO ON PANEL SCHEDULE AND
 SHOW AS DISC.
  
 (9)NOTE: PLEASE SEE RISER SHOWN AS EXIST
 -ING,,,NOTE A/C UNIT BEING FED FROM
 METER???? HOW IS THIS POSSIBLE??
 ALSO 1 1/2" CONDUIT W/ 3-#3`S
 ALSO PLEASE SEE EQUIPMENT GROUNDING
 CONDCUTOE BEING SHOWN FROM METER TO
 MAIN?? PLEASE VERIFY THIS..
  
 10)NOTE: PLEASE SEE PLAN AT GARAGE.
 SUB PANEL "A" IS BEING SHOWN??YET
 PANEL AT MAIN HOUSE AS EXISTING IS SHOWN
 AS "A" PLEASE CORRECT.
  
 11)NOTE: PLEASE SEE PLAN!! MAIN EXISTING
 PANEL IS BEING SHOWN IN NEW PANTRY???
 PLEASE SEE ALL THE REQ`MENTS FOR
 110-26 AND SEE 384-7 FOR EASILY IGNITIB-
 -LE MATERIALS. THIS PANTRY HAS SHELVING
 SHOWN AND DOES NOT MEET ANY OF THE ABOVE
 TWO CODE ARTS: PLEASE NOTE PANEL IS NOT
 PERMITTED IN THIS TYPE OF STORAGE SPACE.
  
 12)NOTE: PLEASE NOTE THAT WATER HEATER
 THAT IS SHOWN ON E-2 IS NOT ON PANEL
 SCHEDULE. PLEASE CLARIFY.
  
 13)NOTE: PLEASE NOTE WARMING DRAWER IS
 NOT SHOWN ON PANEL SCHEDULE???
  
 14)NOTE: PLEASE SHOW CKLARIFICATION ON
 WPGFI SHOWN ON PORCH W/ GAS SHOWN NEXT
 TO IT??
  
 15)NOTE: PANEL SHEDULE SHOWS ELEC COOK
 -TOP AND PLAN SHOWS GAS COOK-TOP??
 PLEASE CORRELATE..
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 ON THE ABOVE OR A MEETING IS PREFERRED
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372