| Plan Review Notes For Permit 00120676 |
| Permit Number |
00120676 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-02-14 00:00:00 | PROVISO:AS PER NFPA 90A 4-4.4.2, DUCT | | | SMOKE DETECTOR SHALL BE TIED WITH | | | BUILDING FIRE ALARM, IF BUILING FIRE | | | ALARM DOES NOT EXIST, DUCT SMOKE | | | DETECTORS SHALL ACTIVATED STROBE/ALARM | | | IN OCCUPIED AREAS. | | | | | | AS PER 97 SMC 609.1.1, NO COMBUSTIBLES | | | SHALL BE ABOVE CEILING IN RETURN AIR | | | PLENUM. | | | | | | FIRE DAMPER IS REQUIRED FOR MOTORIZED | | | DAMPER INTAKE OPENING FOR AHU 1 AS PER | | | 97 610.1.2 (CORRIDOR TO BE PROTECTED | | | PER 97SBC 1006.2.2) |
|