2001-01-08 00:00:00*************** UNSAT *****************
  
 PLANS NEED TO HAVE MORE ELECTRICAL DE-
 -TAIL SHOWN. SEE NOTES TO FOLLOW.
  
  
 1)NOTE: PLEASE NOTE THAT NEW A/C UNIT
 IS NOTED ON PLAN BUT NOT SHOWN ON ELEC
 PLAN.PLEASE SHOW DISC`S PER 440-11
 NEED TO SHOW NEW CU LOCATION.
  
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING NEW A/C LOAD BEING ADDED AND
 SHOW SIZE OF EXISTING SERVICE. 215-5
  
 3)NOTE: PLEASE SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE,
 MUST BE 20A AND #12 PER 210-11-C-3
  
 4)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING PER 210-70 FOR MASTER CLOSETS
  
 5)NOTE:PLEASE NOTE SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS PER NFPA-72 2-2.1.1.1
 SLEEPING ROOMS ARE ROOMS WITH CLOSET AND
 /OR BATHS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  