| Plan Review Notes For Permit 00120669 |
| Permit Number |
00120669 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | PLANS NEED TO HAVE MORE ELECTRICAL DE- | | | -TAIL SHOWN. SEE NOTES TO FOLLOW. | | | | | | | | | 1)NOTE: PLEASE NOTE THAT NEW A/C UNIT | | | IS NOTED ON PLAN BUT NOT SHOWN ON ELEC | | | PLAN.PLEASE SHOW DISC`S PER 440-11 | | | NEED TO SHOW NEW CU LOCATION. | | | | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING NEW A/C LOAD BEING ADDED AND | | | SHOW SIZE OF EXISTING SERVICE. 215-5 | | | | | | 3)NOTE: PLEASE SHOW THE REQ`D DEDICATED | | | BATH(S) CIRCUIT(S) ON PANEL SCHEDULE, | | | MUST BE 20A AND #12 PER 210-11-C-3 | | | | | | 4)NOTE: PLEASE CLARIFY MEANS OF EGRESS | | | LIGHTING PER 210-70 FOR MASTER CLOSETS | | | | | | 5)NOTE:PLEASE NOTE SMOKE DETECTORS | | | ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP- | | | -ING ROOMS PER NFPA-72 2-2.1.1.1 | | | SLEEPING ROOMS ARE ROOMS WITH CLOSET AND | | | /OR BATHS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|