2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1).S.B.C. 104.2.2- MISSING PRODUCT
 APPROVAL REPORTS FOR EXT. DOOR MASTER
 BATH,GLASS BLOCK & FOR THE ROOFING
 MATERIALS, ROOF TILE & STORM SHUTTERS.
 2). S.B.C. 2405.2 SAFETY GLASS- HAZARD-
 OUS AREAS. SHOWER/TUB
 3).CARPORT ENTRANCE- LANDINGS S.B.C.
 1012.1.6.-LANDING REQUIRED, THE LANDING
 MAY BE ONE STEP LOWER THAN THE INSIDE
 FLOOR LEVEL (7" LOWER).
 4).WHIRLPOOL ACCESS REQUIRED FOR MOTOR
 5).SBC 104.2.2- FRENCH DOORS TO BE CUT
 IN, ARE LARGER THAN EXISTING OPENING.
 WILL ADDITIONAL COLUMN REEQUIRRED?
 6).SBC 104.2.2- ADDITIONAL INFO:
 SHEET A-5 DETAILS 1&3 SHOWS A 1/4" RED
 IRON BRACKET, NEED ANCHOR INFORMATION
 TRUSS TO EXISTING BEAM/ BEAM TO COLUMN.
 IS THERE A REDUCTION REQUIRED FOR EDGE
 DISTANCE FOR THE ANCHORS COLUMN/BEAM
 IN DETAIL #1. BOLT SIZE & PLACEMENT
 7).DISCREPANCY, SBC 104.2.2- SHEET A-5
 ROOF FRAMING FOR OPEN TERRACE SHOWS A
 DROPPED TRUSS GABLE WITH OVERHANG.
 DETAIL 2/6 SHOWS A STANDARD GABLE NO
 OVERHANG.
 8).DETAIL 1/6 SHOWS FLOOR JOIST CLOSER
 TO THE SOIL THAN 18" REQUIRES PRESSURE
 TREARED JOIST, SBC 2304.3.4.
 9).CLARIFY, A-4 STEEL COLUMN 2 LOCATIONS
 APPROX. 4'-6" APART "L" SHAPED PLATE
 DOESN'T SHOW ANY LOAD.
 10). NOTE: TO SHORE UP EXISTING BM. IS
 THIS A WOOD BEAM OR CONCRETE & STEEL?
 HOW IS THE ROOF LOADS TO BE CARRIED?
  
 BUILDING PLAN REVIEW