| Permit Number |
00120607 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) SMOKE DETECTORS ARE TO BE INSTALLED A | | | MINIMUM OF AT LEAST THREE FEET FROM | | | AIR CONDITIONING DIFFUSERS. | | | 2) FOUR SIGNALS ARE REQUIRED, GENERAL | | | ALARM, WATERFLOW, GENERAL TROUBLE AND | | | SUPERVISORY. | | | 3) FIRE ALARM SYSTEM IS REQUIRED TO BE | | | MONITORED BY A LICENSED UL LISTED | | | CENTRAL STATION APPROVED BY THE FIRE | | | RESCUE DEPARTMENT. | | | 4) SYSTEM TO BE CLASS A OR FULLY | | | ADDRESSABLE. | | | 5) SYSTEM TO BE TESTED WITH MEMBERS OF | | | THE FIRE RESCUE DEPARTMENT. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 | | | PASSED: SIGNED BY MEC 12/13/00 WITH | | | PROVISO |
|