| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS OF ALL | | | ELECTRICAL EQUIPMENT. MAIN/PANELS/BRKRS | | | ARE TO BE RATED FOR AVAILABLE FAULT | | | CURRENTS. PER 110-9 | | | | | | 2)NOTE: PLEASE SEE ELEC RISER, PLAN | | | SHOWS FEEDS TO LIGHTING AND PERMIT APPL | | | -ICATION HAS SITE LIGHTING CROSSED OFF. | | | PLEASE CLARIFY. | | | | | | 3)NOTE: PLEASE HAVE 100A PANEL INDICATE | | | MCB. | | | | | | 4)NOTE: PLEASE SHOW TWO GRND RODS FOR | | | SERVICE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|