2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1). SECTION 2/1 SHOWS A 1 HR. WALL,
 WP1200 IS NOT LISTED IN THE UL LISTINGS.
 THERE IS A NOTE ON THAT SAME DETAIL :TO
 CONTINUE EVERY OTHER STUD TO UNDERSIDE
 OF ROOF STRUCTURE ABOVE, THIS PUTS THESE
 STUDS AT 4'-0" O.C.PLEASE COPY THE UL
 LISTING
 2). FL ACCESSIBILITY CODE 4.13.6
 MANEUVERING CLEARENCES AT DOORS- 18" ON
 THE LATCH SIDE OF DOORS, FRONT APPROACH
 SEE DOOR "E" IN FRONT OF ROOM 104 STO.
 3). SBC 1001.1.3- MEANS OF EGRESS- MEANS
 OF EGRESS SHALL NOT BE PERMITTED THROUGH
 KITCHENS, CLOSETS,RESTROOMS AND SIMILAR
 AREAS, SEE ROOM 104.
  
 BUILDING PLAN REVIEW