| Plan Review Notes For Permit 00120591 |
| Permit Number |
00120591 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: | | | 1). SECTION 2/1 SHOWS A 1 HR. WALL, | | | WP1200 IS NOT LISTED IN THE UL LISTINGS. | | | THERE IS A NOTE ON THAT SAME DETAIL :TO | | | CONTINUE EVERY OTHER STUD TO UNDERSIDE | | | OF ROOF STRUCTURE ABOVE, THIS PUTS THESE | | | STUDS AT 4'-0" O.C.PLEASE COPY THE UL | | | LISTING | | | 2). FL ACCESSIBILITY CODE 4.13.6 | | | MANEUVERING CLEARENCES AT DOORS- 18" ON | | | THE LATCH SIDE OF DOORS, FRONT APPROACH | | | SEE DOOR "E" IN FRONT OF ROOM 104 STO. | | | 3). SBC 1001.1.3- MEANS OF EGRESS- MEANS | | | OF EGRESS SHALL NOT BE PERMITTED THROUGH | | | KITCHENS, CLOSETS,RESTROOMS AND SIMILAR | | | AREAS, SEE ROOM 104. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|