| Plan Review Notes For Permit 00120570 |
| Permit Number |
00120570 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-03-13 00:00:00 | PROVISO: | | | ADDITIONAL INFORMATION IS TO BE PROVIDED | | | PRIOR TO ANY MECHANCIAL PERMIT OR WORK | | | IN THIS SPACE. | | | PROVIDE INFORMATION ON ZONES TO BE RUN | | | IN A NEGATIVE PRESSURE,AIR BALANCE AND | | | FAN OPERATION. | | | PROVIDE INFORMATION ON VENTILATION FOR | | | STORAGE ROOMS IN EVENT OF POWER | | | FAILURE | | | PROVIDE INFORMATION ON DETECTION | | | SYSTEM,BOTH NORMAL OPERATION AND IN THE | | | EVENT OF A POWER FAILURE. |
|