| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PLEASE INDICATE THE TYPE OF BUSINESS | | | THERMO SEPARATION PRODUCTS IS. WHAT WILL | | | THE TENANT SPACE BE USED FOR. | | | 2) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. THE PLANS INDICATES THAT | | | THE TENANT SPACE WILL BE FIRE SPRINKLER | | | PROTECTED. | | | 3) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON DRAWINGS. THE FIRE ALARM NOTES | | | SECTION INDICATES CLASS B, STYLE C FIRE | | | ALARM CIRCUITS. ONLY CLASS A, STYLE D | | | FIRE ALARM CIRCUITS ARE PERMITTED. | | | 4) PLEASE PROVIDE MORE DETAILS ON | | | CHEMICAL HOOD / VENT SHOWN ON PAGE A4.0 | | | 5) PLEASE PROVIDE MORE DETAILS ON FIRE | | | SHUTTERS. PRODUCT DATA IS REQUESTED. | | | 6) PLEASE PROVIDE MORE DETAILS ON | | | NITRO STORAGE, 163. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|