| 2001-01-08 00:00:00 | BUILDING PLAN RREVIEW |
| | WECAN'T DO A COMPETANTAND THOUROUGH |
| | REVIEW OF THE PLANS WITH OUT ADDITIONAL |
| | INFORMATION, WE WILL REQUIRE AMSDA |
| | LISTINGS SHEET, (MATERIALS SAFETY DATA |
| | SHEET) OF ALL HAZARDOUS MATERIALS WITH |
| | TYPE OF HAZARD GROUP/ CLASS, QUANITY, |
| | IF LIQUID, SOLID OR GAS. |
| | 1).WHAT TYPE OF BUSINESS IS THIS, THERE |
| | IS CLASSROOMS,LABS ETC, IS THIS EDUCA- |
| | TIONAL? |
| | 2). ROOM #159 ITS- WHAT IS THIS ROOM TO |
| | BE USED FOR? |
| | 3). ROOM #155 CONTAINMENT ROOM- WHAT |
| | TYPE OF MATERIALS ARE TO BE STOED IN |
| | THIS ROOM? IS THERE GOING TO BE MORE |
| | THAN THE (2) 55 GAL DRUMS? |
| | 4).R00M #154 STORAGE, IS THERE GOING TO |
| | HAVE ANY TYPE OF HAZARDOUS STORAGE THERE |
| | 5).CLOSETS 103,103A, 107 & A07A SHOW |
| | THAT THEY ARE TO BE CONTROLED AREAS |
| | CONTAINING HAZARDOUS MATERIALS NOT EX- |
| | CEEDINGTHE EXEMPT QUANITIES,WHAT TYPE |
| | OF MATERIALS ARE TO BE STORED IN THESE |
| | AREAS/ QUANITITIES? |
| | CLOSETS 103,103A,107, 107A & 155 ARE TO |
| | COMPLY WITH S.B.C. 308.2.2 WITH 3/4HR |
| | OPENING PROTECTION WITH SELF CLOSING OR |
| | AUTOMATIC CLOSING DEVISE IN ACCORDANCE |
| | WITH 705.1.3.2.3. |
| | 6). S.B.C.407.1.3.5-LABORATORY FUME HOOD |
| | WHERE FLAMMABLE MATERIALS ARE TO BE USED |
| | SHALL BE PROTECTED BY AN AUTOMATIC |
| | SPRINKLER SYSTEM. |
| | 7). DEPENDING ON THE AMOUNTS OF HAZARD- |
| | OUS MATERIALS STORED, THESE CODE SECTION |
| | MAY BE APPLICABLE: |
| | S.B.C. 407.2.3.1 SPILL CONTROL, DRAINAGE |
| | AND CONTAINMENT. |
| | S.B.C. 407.2.3.3 DRAINAGE |
| | S.B.C. 407.2.3.4 SECONDARY CONTAINMENT |
| | VENTILATION, ALARMS , DETECTION & |
| | FIRE SPRINKLER SYSTEM. |
| | |