| Plan Review Notes For Permit 00120567 |
| Permit Number |
00120567 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE DEPARTMENT CONNECTION TO BE | | | LOCATED WITHIN 150 FEET OF A FIRE | | | HYDRANT. | | | 2) PLEASE PROVIDE MORE DETAILS ON RACKS | | | PLANNED FOR USE. | | | 3) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL ELECTRICAL, MECHANICAL AND SERVICE | | | ROOMS. | | | 4) SYSTEM TO BE PRESSURE TESTED FOR TWO | | | HOURS ARE REQUIRED BY CODE. | | | 5) FIRE SPRINKLER SYSTEM TO BE INSTALLED | | | IN ACCORDANCE WITH ALL APPLICABLE NFPA | | | FIRE SPRINKLER CODES. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|