| Plan Review Notes For Permit 00120524 |
| Permit Number |
00120524 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-03 00:00:00 | 1) PLEASE INDICATE ON PLANS THAT ANY | | | ACTIVATION OF THE FIRE ALARM SYSTEM OR | | | FIRE SPRINKLER SYSTEM SHALL IMMEDIATELY | | | CAUSE THE STAIRWAY AND ELEVATOR SHAFT | | | PRESSURIZATION FANS TO ACTIVATE. THESE | | | SYSTEMS ARE ALSO TO BE CONNECTED TO | | | EMERGENCY POWER SYSTEMS FOR THE | | | BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|