2001-03-14 00:00:00*****************TRUSSES****************
  
 1) MEAN ROOF HEIGHT ON TRUSS DRAWINGS IS
 15 FT. AND THE MRF ON THE DESIGN
 COMPLIANCE FORM SUBMITTED WITH THE
 PLANSIS 16 FT. PLEASE CORRECT.
  
 2) TRUSS LAYOUT MUST HAVE WET
 SIGNATURE,DATE AND EMBOSSED SEAL OF THE
 ENGINEER
 AND THE ENGINEERS TITLE BLOCK PER
 61G15-23.002 F.A.C.
  
 3) TRUSS DRAWINGS NEED TO HAVE
 ENGINEERSWET SIGNATURE, SIGNATURE STAMP
 IS NOT
 ACCEPTABLE.
  
 4) INSTALLATION AND BRACING SHEETS ARE
 MISSING.
  
 5) SPECIFY UPLIFT AND ANCHORS FOR
 GIRDERFG5.
  
 6) SPECIFY UPLIFT AND ANCHORS USED TO
 CONNECT TRUSSES TO GIRDERS AT OPEN
 PORCHAND AT LEFT OF GARAGE. GIRDERS
 FG2B,FG5 AND FG2A.
  
 7) TRUSSES HJH, HJI, HJJ HAVE UPLIFT
 VALUES ON TRUSS DRAWINGS WHICH EXCEED
 THOSE ON PLANS. PLEASE CORRECT.
  
 8) PROVIDE DETAILS OF CONNECTION BETWEEN
 GROUTED BLOCK COLUMNS AND WOOD GIRDERS
 AT COVERED PORCH. SPECIFY ANCHOR
 CAPACITIES AND UPLIFT LOADS. REVISED BY
 ARCHITECT IN LETTER DATED FEB.5,2001.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202