| 2001-03-14 00:00:00 | *****************TRUSSES**************** | | | | | | 1) MEAN ROOF HEIGHT ON TRUSS DRAWINGS IS | | | 15 FT. AND THE MRF ON THE DESIGN | | | COMPLIANCE FORM SUBMITTED WITH THE | | | PLANSIS 16 FT. PLEASE CORRECT. | | | | | | 2) TRUSS LAYOUT MUST HAVE WET | | | SIGNATURE,DATE AND EMBOSSED SEAL OF THE | | | ENGINEER | | | AND THE ENGINEERS TITLE BLOCK PER | | | 61G15-23.002 F.A.C. | | | | | | 3) TRUSS DRAWINGS NEED TO HAVE | | | ENGINEERSWET SIGNATURE, SIGNATURE STAMP | | | IS NOT | | | ACCEPTABLE. | | | | | | 4) INSTALLATION AND BRACING SHEETS ARE | | | MISSING. | | | | | | 5) SPECIFY UPLIFT AND ANCHORS FOR | | | GIRDERFG5. | | | | | | 6) SPECIFY UPLIFT AND ANCHORS USED TO | | | CONNECT TRUSSES TO GIRDERS AT OPEN | | | PORCHAND AT LEFT OF GARAGE. GIRDERS | | | FG2B,FG5 AND FG2A. | | | | | | 7) TRUSSES HJH, HJI, HJJ HAVE UPLIFT | | | VALUES ON TRUSS DRAWINGS WHICH EXCEED | | | THOSE ON PLANS. PLEASE CORRECT. | | | | | | 8) PROVIDE DETAILS OF CONNECTION BETWEEN | | | GROUTED BLOCK COLUMNS AND WOOD GIRDERS | | | AT COVERED PORCH. SPECIFY ANCHOR | | | CAPACITIES AND UPLIFT LOADS. REVISED BY | | | ARCHITECT IN LETTER DATED FEB.5,2001. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|