2001-01-25 00:00:00****************REVSION NEEDED********
  
  
  
  
  
  
  
  
  
  
  
  
  
 3)NOTE: PLEASE NOTE THAT THE PANEL AT
 POOL HOUSE STILL DOES NOT INDICATE BEING
 MAIN BREAKER? MAIN DISCONNECT THAT IS
 SHOWN IS TO BE GROUPED WITH MAIN AT
 HOUSE PER 230-72. SEE NOTE FROM FISRT
 REVIEW.GROUNDING AT THAT DISCONNECT IS
 TO BE THE GROUNDING AT PANEL AT
 POOLHOUSE.
 PANEL SCHEDUEL DOESN'T INDICATE BEING
 MCB EITHER. PLEASE CLARIFY LOCATIONS OF
 EQUIPMENT. THE POOL HOUSE PANEL IS THE
 ONLY ONE BEING SHOWN?
  
  
 PLEASE CLARIFY AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW BEFORE ANY
 INSPECTION IS CALLED. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW