2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE ELECTRICAL NOTE
 BELOW RISER. NOTE MENTIONS ALL OUTLETS
 WITHIN 6` OF WATER SOURCE. THAT WAS FROM
 THE "96" NEC. ALL OUTLET SERVING
 COUNTERPSPACE/ GARAGES/ BATHS ARE TO BE
 GFI/GFI PROTECTED. PER 210-8
 PLEASE CHANGE OR REMOVE NOTE.
  
 2)NOTE: PLEASE SEE RISER,,, PANEL"B " IS
 SHOWN ON RISER AS EXISTING. PLEASE SHOW
 LOCATION OF MAINS. MAINS NEED TO BE
 GROUPED PER 230-72 MAIN FOR PANEL "B"
 IS WHERE NOW? IF EXISTING WHAT DOES IT
 FEED?
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED. MAINS
 /PANELS.BRKRS ARE ALL TO BE RAATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9
  
 4)NOTE; PLEASE SHOW ALL GROUNDING AT
 DETACHED POOL HOUSE PER 250-50. COLD
 WATER PIPE AND NEW BLDG STEEL.
  
 5)NOTE: PLEASE SHOW MEANS OF DISCONNECT
 AT DETACHED BLDG. MCB? DISC? ETC.
  
 6)NOTE: NOTE,, RISER SHOWS EQUIPMENT
 GROUNDING CONDUCTOR FROM METER TO MAIN
 /PANEL.PLEASE VERIFY.
  
 7)NOTE: PLEASE SHOW MEANS OF EGRESS
 LIGHTING FROM GARAGE INTO STORAGE?" 210-
 -70. 3-WAY?
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372