2001-01-08 00:00:001) THE APARTMENTS ON BOTH FLOORS ARE TO
 BE COMPLETELY FIRE SPRINKLER PROTECTED.
 THE ONLY EXCEPTIONS TO THIS ARE,
 BATHROOMS UNDER 55 SQUARE FEET AND
 CLOSETS UNDER 24 SQUARE FEET.
 2) NO OBSTRUCTIONS TO FIRE SPRINKLERS
 WILL BE PERMITTED. SOFFITS ARE NOT TO
 INTERFERE WITH FIRE SPRINKLER HEAD
 DISCHARGE PATTERNS.
  