Plan Review Notes
Plan Review Notes For Permit 00120260
Permit Number 00120260
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISOS.
 1. NO TREES SHALL BE PLANTED WHERE
 WATER SERVICE LINE TRAVELS THRU SITE
 2. PROVIDE A BALVE BETWEEN POTABLE WATER
 SERVICE AND IRRIGATION SERVICE WHICH
 WILL ENABLE TO SUCH DOWN ONE SYSTEM
 WITHOUT AFFECTING THE OTHER.
 3. BACKFLOW DETAIL SHOWN IS NOT OUR
 STANDARD BACKFLOW DETAIL.
 (CONTRACTOR TO COORDINATE WITH ORVILLE
 POLK, BACKFLOW SPECIALIST WHEN SETTING
 THEM 561 659 8079.
 4. 5' UTILITY EASEMENT ACROSS SITE
 MAY NOT BE NEEDED, COORDINATE WITH
 OUR SURVEY DIVISION TO HAVE IT REMOVED.
 5. PROPOSED 1" VALVESSHALL BE ENCLOSED
 IN ONE OF OUR STANDARD METER BOXES WHICH
 PROVIDES A LOCKING LID.
 6. PROVIDE PERVIOUS AND IMPERVIOUS CAL
 CULATION ALONG WITH PROPERTY CONTROL
 NUMBER AND ADDRESS OF PARK TO
 MANNY GONZALEZ, PUBLIC UTILITIES ENG.
 1000 45TH STREET SUITE 15, WPB, FL 33407
 TOTAL SITE S.F. AND ACRES SHALL BE
 PROVIDED. YOU MAY FAX THIS INFORMATION
 TO OUR OFFICE. 561 659 8039.
 IF ANY QUESTIONS FEEL FREE TO CONTACT
 ME AT 561 659 8040 EXT. 2306
 7. A PROTECTIVE/SILT FENCE SHALL BE PROV
 IDED ALONG THE PERIMETER OF THE SITE
 TO AVOID PEDESTRIANS AND TO AVOID
 POLLUTION.
 8. IN AND OUT TRAFFIC MUST BE WASHED
 IN A MANNER SO THAT DIRT DOES NOT LEAVE
 SITE.
 9. ON THE COVER SHEET PLEASE PROVIDE
 SECTION TOWNSHIP AND RANGE.