| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: | | | 1).1707.4.1 IMPACT RESISTANT GLAZING | | | SYSTEMS REQUIRED. IF THE STORE FRONT | | | GLAZING SYSTEM DOESN'T COMPLY WITH THE | | | LARGE MISSLE IMPACT TEST, STORM SHUTTERS | | | THAT HAVE APPROVAL ARE REQUIRED. | | | 2).SBC 3106.2 FABRIC AWNINGS OR CANOPIES | | | REQUIRE FLAME RESISTANT MATERIALS. | | | 3).SPRINKLER SYSTEM PLANS NOT INCORPARA- | | | TED IN PLANS. | | | 4). 104.2.2 ADD INFO ON SOFFIT DETAILS, | | | NOTE SAID TO:ATTACHSOFFIT VERTICAL | | | STUDS TO STRUCTURE ABOVE.WHAT TYPE OF | | | SHOT, &HOW OFTEN? HOW OFTEN IS THE | | | DROPPED CEILING TO BE SUPPORTED & WITH | | | WHAT GAUGE HANGER WIRE? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|