2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1).1707.4.1 IMPACT RESISTANT GLAZING
 SYSTEMS REQUIRED. IF THE STORE FRONT
 GLAZING SYSTEM DOESN'T COMPLY WITH THE
 LARGE MISSLE IMPACT TEST, STORM SHUTTERS
 THAT HAVE APPROVAL ARE REQUIRED.
 2).SBC 3106.2 FABRIC AWNINGS OR CANOPIES
 REQUIRE FLAME RESISTANT MATERIALS.
 3).SPRINKLER SYSTEM PLANS NOT INCORPARA-
 TED IN PLANS.
 4). 104.2.2 ADD INFO ON SOFFIT DETAILS,
 NOTE SAID TO:ATTACHSOFFIT VERTICAL
 STUDS TO STRUCTURE ABOVE.WHAT TYPE OF
 SHOT, &HOW OFTEN? HOW OFTEN IS THE
 DROPPED CEILING TO BE SUPPORTED & WITH
 WHAT GAUGE HANGER WIRE?
  