2001-01-08 00:00:00PROVISO:
 1. NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM (ABOVE CEILING AREA) PER 1997 SMC
 609.1.1
 2. M-1 ASHRAE 62-89 CALCS SHOW 1000CFM
 CORRECT NOTE ON M-2 FROM 100 CFM TO 1000
 CFM TO BE CONSISTANT W/ CALCS
 3. LOCAL ORDINANCE REQUIRES MINIMUM OF
 18" BETWEEN ROOF SURFACE AND BOTTOM OF
 STAND, NOT 14" AS SHOWN ON PLAN. PROVIDE
 18" MINIMUM CLEARANCE