| 2001-01-08 00:00:00 | PROVISO: | | | 1. NO COMBUSTIBLES ALLOWED IN RETURN AIR | | | PLENUM (ABOVE CEILING AREA) PER 1997 SMC | | | 609.1.1 | | | 2. M-1 ASHRAE 62-89 CALCS SHOW 1000CFM | | | CORRECT NOTE ON M-2 FROM 100 CFM TO 1000 | | | CFM TO BE CONSISTANT W/ CALCS | | | 3. LOCAL ORDINANCE REQUIRES MINIMUM OF | | | 18" BETWEEN ROOF SURFACE AND BOTTOM OF | | | STAND, NOT 14" AS SHOWN ON PLAN. PROVIDE | | | 18" MINIMUM CLEARANCE |
|