Plan Review Notes
Plan Review Notes For Permit 00120164
Permit Number 00120164
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE RISER DIAGRAMAND
 PLANS. WHERE IS TRANSFORMER LOCATED AND
 IS FEEDERS FROM TRANS FORMER TO PANEL
 LONGER THAN 25`????
  
 2)NOTE: PLEASE SHOW LOAD CALCULATION.
 SQ. FT. ECT.ALL CONTINUOUS LOADS AT 125%
  
 3)NOTE: PLEASE NOTE AND SHOW TRANSFORMER
 LOCATION.
  
 4)NOTE: PLEASE SHOW AIC RATINGS FOR ALL
 ELECTRICAL EQUIPMENT. ALL MAINS/PANELS
 AND BRKRS ARE TO BE RATED FOR THE AVAIL-
 -ABLE FAULT CURRENT PER 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372