| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAMAND | | | PLANS. WHERE IS TRANSFORMER LOCATED AND | | | IS FEEDERS FROM TRANS FORMER TO PANEL | | | LONGER THAN 25`???? | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATION. | | | SQ. FT. ECT.ALL CONTINUOUS LOADS AT 125% | | | | | | 3)NOTE: PLEASE NOTE AND SHOW TRANSFORMER | | | LOCATION. | | | | | | 4)NOTE: PLEASE SHOW AIC RATINGS FOR ALL | | | ELECTRICAL EQUIPMENT. ALL MAINS/PANELS | | | AND BRKRS ARE TO BE RATED FOR THE AVAIL- | | | -ABLE FAULT CURRENT PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|