| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | | | | 1.FITTING ROOM MUST COMPLY WITH 97 FACBC | | | 4.35.2 AND 4.35.4. | | | | | | 2.MINIMUM SIZE OF BATHROOM FLOOR DRAINS | | | IS 3" SPC 409.4.1.1. PAGE P1.2 SAN. | | | RISER SHOWS 2" FLOOR DRAINS. | | | | | | 3.ONE HIGH LOW DRINKING FOUNTAIN | | | REQUIRED TO MEET FACBC 4.1.3(10) AND | | | TABLE 407 94 SPC. | | | | | | 4.FLOOR DRAIN IN MECH ROOM MUST BE FLOOR | | | DRAIN NOT FUNNUL DRAIN. COUNTY | | | ADMENDMENTS 507.6.2. | | | | | | 5.DRAIN FROM WATER HEATER PAN DRAIN MUST | | | BE 1" SPC 507.8.2. | | | | | | 6.RELIEF VALVE SHALL BE PIPED FULL SIZE | | | SEPARATELY. SPC 507.8.4. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|