| Plan Review Notes For Permit 00120094 |
| Permit Number |
00120094 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | | | | 1. SIGNED AND SEALED DRAWINGS REQUIRED | | | FOR REVIEW | | | 2. BATHROOM EXHAUST FANS TO RUN ANY TIME | | | THE BUILDING IS OCCUPIED AND THE AHU IS | | | RUNNING. | | | 3. ALL CONDENSING UNITS ON GROUND SHALL | | | BE MOUNTED ON SOLID CONCRETE PADS MIN. | | | 3" ABOVE FINISHED GRADE. | | | 4. NFPA 90A 4-4.4.3 REQUIRES NOTIFICATIO | | | TO BLDG FIRE ALARM OR HORN AND STROBE ON | | | ACTIVATION OF DUCT SMOKE DETECTOR |
|