| Plan Review Notes For Permit 00120094 |
| Permit Number |
00120094 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS | | | REQUIRED PER CITY CODE REQUIREMENTS. | | | 2) PROVIDE COMPLETE FIRE SPRINKLER | | | SYSTEM PLANS AND PERMIT TO THE | | | CONSTRUCTION SERVICES DEPARTMENT PRIOR | | | TO COMMENCING ANY WORK. HYDRAULIC | | | CALCULATIONS ARE TO BE PROVIDED. | | | 3) FIRE SPRINKLER SYSTEM TO BE | | | SUPERVISED BY AN APPROVED CENTRAL | | | STATION APPROVED BY THE FIRE RESCUE | | | DEPARTMENT. | | | 4) PROVIDE FIRE EXTINGUISHER WITH | | | CURRENT SERVICE TAG IN PRO-SHOP. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|