2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW MEANS OF DISCONNECT
 FOR POWER/LIGHTING AT GAZEBO(S).
  
 2)NOTE: PLEASE SHOWALL CONTINUOUS LOAD
 -S AT 125% AND 125% FOR LARGEST MOTOR.
  
 PLEASE MAKE SURE THE PLANS THAT ARE
 SUBMITTED FOR PERMIT ARE SIGNED AND
 SEALED BY THE ENGINEER OF RECORD PER
 61G15-23.002 AND CHAPTER 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372