| Plan Review Notes For Permit 00120092 |
| Permit Number |
00120092 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE 210-8-A-6 AND SHOW | | | ALL OUTLETS SERVING KITCHEN COUNTER- | | | SPACE AS GFI/ GFI PROTECTED. | | | | | | 2)NOTE: PLEASE NOTE THAT NO SECOND FLOOR | | | ELECTRICAL WAS SUBMITTED FOR CARRIAGE | | | HOUSE.?? | | | | | | 3)NOTE: PLEASE SEE 210-8 FOR GARAGE | | | GFI PROTECTION. | | | | | | 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | AND SHOW RISER DIAGRAM TO SHOW EXISTING | | | SERVICE EQUIPMENT SIZES. PLAN SHOWING | | | NEW POOL/ A/C EQUIPMENT. PLEASE SUBMIT | | | NEW PANEL SCHEDULES. | | | | | | 5)NOTE: PLEASE NOTE MISSING GFI OUTLET | | | FOR A/C EQUIPMENT. PER MECH CODE 300.9 | | | | | | 6)NOTE:PLEASE SEE LOCATION OF OUTLET | | | SERVING BATH IN CARR. HOUSE. PER 210-52D | | | AND SEE 210-11-C-3 FOR REQ`MNETS OF | | | CIRCUIT. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|