| Date |
Text |
| 2001-04-19 00:00:00 | CHECKLIST: |
| | 1-REAR ELEVATION EXCEEDS THE AMOUNT OF |
| | OPENINGS ALLOWED BY TABLE 600 SBC/97. |
| | NOT DONE FROM PREVIOUS CHECKLIST. |
| | 2-SUBMIT COMPLETE SET OF ENGINEERED |
| | DRAWINGS FOR ROYAL WALL SYSTEM |
| | SHOWING ALL PANELS AND REINFORCING. |
| | 3-PROVIDE PRODUCT APPROVAL FOR: |
| | -SLIDING GLASS DOORS WITH THE SIZE |
| | SHOWN ON PLANS AND ELEVATIONS. (8' HI) |
| | -ARCHED AND RECTANGUALAR WINDOWS WITH |
| | THE SIZE SHOWN ON PLANS & ELEVATIONS. |
| | NOTE: MULLIONS PRODUCT APPROVAL IS FOR |
| | WINDOWS FROM THE SAME MANUFACTURER. |
| | ARCHED WINDOWS SUBMITTED ARE FROM |
| | LAWSON AND FIXED WINDOWS ARE FROM PGT |
| | THIS IS NOT ALLOWED. |
| | -FLAT ROOF SYSTEM. ITEM SUBMITTED ARE |
| | THE SPECS. WE NEED THE ACTUAL PRODUCT |
| | APPROVAL AS WELL. |
| | 4-OWES $1806.45 FOR LOW VALUATION, RADON |
| | AND WESTERN EXPANSION FEES. |
| | 5-PROVIDE COMPLETE INFORMATION FOR |
| | STORM PANELS UNDER A SEPARATE PERMIT. |
| | 6-PROVIDE COMPLETE DETAILS FOR THE |
| | CONSTRUCTION OF THE WINDOW SEAT. |
| | SKETCH SUBMITTED NEEDS ADDITIONAL |
| | INFORMATION LIKE: FRAMING FOR WINDOW, |
| | REINFORCEMENT TO RECEIVE STORM PANELS, |
| | WHY IS ONLY ONE 2X TOP PLATE?, WINDOW |
| | HEADER, GABLE END DETAIL, ETC. |
| | MAKE THESE DRAWINGS PART OF THE SET, |
| | NOT A SEPARATE SHEET. |
| | 7-RAILING DRAWINGS TO BE SITE SPECIFIC |
| | FOR THIS JOB, NOT GENERAL DETAILS. SEE |
| | ACTUAL INSTALLATION CONDITIONS SHOWN |
| | ON PROFESSIONAL OF RECORD DRAWINGS. |
| | -HOW IS THE RAILING ATTACHED TO THE |
| | GLULAM BEAM AND TO THE STEEL COLUMN? |
| | -BOTTOM RAIL SHALL NOT ALLOW 2" SPHERE |
| | TO PASS THRU. SEC 1015.3 SBC 1997. |
| | -ENGINEER OF RECORD TO REVIEW THESE |
| | DRAWINGS PRIOR TO SUBMITTAL. |
| | -ENGINEER FOR RAILING SYSTEM TO DATE |
| | DRAWINGS AS REQUIRED BY CHAPTER 471 |
| | OF FLORIDA STATUTES. |
| | 8-FLOOR PLANS AND EXTERIOR ELEVATIONS |
| | DON'T MATCH. SEE NUMBER OF WINDOWS AND |
| | LOCATION SHOWN ON PLANS VS ELEVATION |
| | AT LEFT SIDE. |
| | 9-SEE COMMENTS BY ZONING. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 659-8096 EXT. 8232. |