| 2001-03-12 00:00:00 | CHECKLIST: |
| | 1-REAR ELEVATION EXCEEDS THE AMOUNT OF |
| | OPENINGS ALLOWED BY TABLE 600 SBC/97. |
| | 2-SUBMITCOMPLETE SET OF ENGINEERED |
| | DRAWINGS FOR "ROYAL WALL" SYSTEM |
| | SHOWING ALL PANELS REINFORCING. |
| | 3-PROVIDE CURRENT SBCCI OR DADE COUNTY |
| | PRODUCT APPROVAL FOR: |
| | -SLIDING GLASS DOORS (EXPIRED). |
| | -GARAGE DOOR THAT MEET THE MINIMUM |
| | DESIGN PRESSURE CALCULATED BY THE |
| | ENGINEER (SEE ROOF FRAMING PLAN). |
| | -ARCHED WINDOW ABOVE ENTRY DOORS. |
| | -FLAT ROOF SYSTEM. |
| | 4-OWES $1806.45 FOR LOW VALUATION, RADON |
| | FEES AND WESTERN EXPANSION FEES. |
| | PLEASE PAY ATTACHED RECEIPT. |
| | 5-STORM PANELS: |
| | -PROVIDE COMPLETE INFORMATION INCLUDING |
| | A KEY PLAN AND INSTALLATION SCHEDULE. |
| | -CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE & |
| | SPACING TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | PANEL SPAN, EDGE DISTANCE, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO. |
| | -MAY APPLY FOR A SEPARATE PERMIT. |
| | 6-REVISE ENERGY CALCULATIONS: |
| | -SEE ROYAL WALL DRAWINGS FOR INSULATION |
| | & MATERIALS USED IN THIS CONSTRUCTION. |
| | -EXTERIOR FRAMING IS NOT INCLUDED IN |
| | THE CALCULATIONS. WHY IS IT MISSING? |
| | 7-SOIL TEST REPORT: ENGINEER DIDN'T |
| | PROVIDE ORIGINAL SIGNATURE AS REQUIRED |
| | BY CHAPTER 471 OF FLORIDA STATUTES. |
| | 8-PROVIDE COMPLETE DETAIL/SECTION THRU |
| | WINDOW SEAT AT GARAGE. |
| | 9-SURVEY DOESN'T SHOW THE DRIVEWAY, BUT |
| | A TEMPORARY WALKWAY. DRIVEWAY PERMIT |
| | CAN NOT BE ISSUED IF DRIVEWAY IS NOT |
| | SHOWN. |
| | 10-SCREEN BUILDERS INC. DRAWINGS TO BE |
| | SITE SPECIFIC. SHOW DETAILS THAT APPLY |
| | TO ACTUAL INSTALLATION. |
| | -BOTTOM RAIL SHALL NOT ALLOW A 2" |
| | SPHERE TO PASS THRU. SEC 1015.3 SBC/97 |
| | NOTE: ENGINEER OF RECORD TO REVIEW |
| | THESE SHOP DRAWINGS PRIOR TO SUBMITTAL |
| | TO THIS OFFICE. PROVIDE GENERAL STAMP |
| | FOR SHOP DRAWINGS REVIEW. |
| | 11-FLOOR PLANS AND EXTERIOR ELEVATIONS |
| | DON'T MATCH. SEE SLIDING GLASS DOORS |
| | AT GRAND RM & WINDOWS AT CAFE AREA. |
| | 12-REVISE SPACING OF STEEL COLUMNS THAT |
| | ARE BETWEEN THE STAIRS. THERE SHALL BE |
| | 36" MINIMUM CLEAR WIDTH OF STAIRS AS |
| | REQUIRED BY SEC 1007.6.3 SBC 1997. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | NOTES: |
| | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ, BUILDING PLAN REVIEWER, AT |
| | 659-8096 EXT. 8232. |