Plan Review Notes For Permit 00120087
Permit Number 00120087
Review Stop E
Sequence Number 2
Notes
Date Text
2001-02-22 00:00:00*********** PROVISO/ REVISION ********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 PLEASE SUBMIT THE REVISIONFOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372