Plan Review Notes
Plan Review Notes For Permit 00120087
Permit Number 00120087
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-10 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-SURVEY DOESN'T MATCH PLANS.
 -PLAT MUST BE RECORDED AND SURVEY
 UPDATED.
 3-ENGINEER OF RECORD TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER 471
 OF FLORIDA STATUTES.
 -ENGINEER TO PROVIDE ORIGINAL SIGNATURE
 ON ALL DOCUMENTS SUBMITTED FOR PUBLIC
 RECORDS.
 4-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS FOR "ROYAL WALL" SYSTEM FOR
 THIS SPECIFIC HOUSE.
 -NOTE: IF HOUSE IS TO BE LOCATED AT
 ZERO LOT LINE, THEN, THE 2" CONCRETE
 PANEL WILL NOT PROVIDE THE ONE HOUR
 FIRE RATING REQUIRED BY TABLE 600.
 TABLE 709.2.1.1 SBC 1997.
 -MAKE SURE ENGINEERED SET OF DRAWINGS
 HAVE THE ENGINEER'S INFORMATION AS
 REQUIRED BY FLORIDA STATUTES. 471.
 5-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -ENTRY DOORS.
 -SLIDING GLASS DOORS OF SIZES SHOWN ON
 PLANS. (EXPIRED )
 -GARAGE DOOR THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD. ALSO, REPORT TO BE LEGIBLE.
 -FIXED AND ROUND WINDOWS.
 -SINGLE HUNG WINDOWS.
 -WINDOW MULLIONS.
 -GLASS BLOCK (1 HR AT ZERO LOT LINE)
 -FLAT ROOF SYSTEM AT BALCONY.
 6-VALUE DECLARED ON APPLICATION IS VERY
 LOW. OWES ADDITIONAL PERMIT FEES OF
 $1056.45 INCLUDING RADON FEES. AND,
 $750 FOR WESTERN EXPANSION IMPACT FEES
 7-STORM PANELS:
 -PROVIDE A KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE (AS PER CITY
 SAMPLE ATTACHED).
 -CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO
 THE MEAN ROOF HEIGHT,DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 8-SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION AT 2ND FLOOR FRAMING PLAN.
 SECTION 2305.2 SBC 1997.
 9-SEE ADDITIONAL COMMENTS ON PLANS,
 INCLUDING THOSE BY THE OTHER TRADES.
 10-REVISE ENERGY CALCULATIONS:
 -NUMBER OF BEDROOMS IS 5. SEE PLANS.
 -ORIGINAL SIGNATURES @ BOTTOM OF FORM.
 11-SOIL TEST REPORT:
 -PROVIDE COMPLETE SOIL TEST REPORT AS
 PER SECTION 1804.2 OF CITY AMENDMENTS.
 -REPORT TO HAVE ORIGINAL SIGNATURE AS
 PER 471 FLORIDA STATUTES.
 12-PROVIDE COMPLETE DETAIL/SECTION THRU
 CUPOLA. SPECIFY ALL CONNECTORS.
 SECTION 104.2.2 CITY AMENDMENTS.
 13-DESIGN CERTIFICATION FOR BUILDING
 CODE COMPLIANCE FORM:
 -USE CITY FORM.
 -NEED ORIGINAL SIGNATURE AS PER 471 OF
 FLORIDA STATUTES.
  
  
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW PROCESS
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
 -ONLY TWO SETS OF DRAWINGS AND SUBMITTAL
 ARE REQUIRED.
2001-01-08 00:00:00CHECKLIST:
 1-