| 2001-01-08 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: PER F.A.C. ALL PLANS THAT ARE |
| | SIGNED AND SEALED BY AN ARCH OR ENGINEER |
| | MUST HAVE THE RAISED SEAL CLEARLY |
| | VISIBLE. ALSO ALL PLANS THAT ARE SIGNED |
| | AND SEALED MUST CONTAIN A TITLE BLOCK |
| | OF THE ARCH OR ENGINEER OF RECORD. |
| | PLEASE SEE F.A.C 61G15-23.002 AND 61G16 |
| | ALSO CHAPTERS 481.221 AND 471.025 |
| | |
| | 2)NOTE: PLEASE SHOW COLD WATER PIPE AS |
| | PART OF THE GROUNDING ELECTRODE SYSTEM |
| | PER 250-5O OR CLRIFY IF CPVC. |
| | |
| | 3)NOTE: PLEASE SEE RISER DIAGRAM. PANEL |
| | IS SHOWN NEXT TO METERCAN. PLANS SHOW |
| | ON THE OTHER SIDE OF HOUSE. PLEASE |
| | CLARIFY IF PANEL IS FED UNDER GROUND |
| | AND IF PANEL IS MCB? |
| | |
| | 4)NOTE: PLEASE NOTE PER NFPA-72 2-2.1.1- |
| | .1 . A SMOKE DETECTOR IS REQ`D ON EACH |
| | LEVEL OF DWELLING. |
| | |
| | 5)NOTE: PLEASE NOTE THAT NO CATV OR |
| | TELEPHONE OUTLETS ARE SHOWN? IF THESE |
| | ITEMS ARE GOING TO BE INSTALLED ? THEN |
| | ALL MUST BE ON PLANS. |
| | |
| | 6)NOTE: PLEASE SEE SECOND FLOOR PLAN. |
| | OUTLETS MISSING PER 210-52 IN BEDROOM? |
| | AND OUTLET PER 2` OF WALL 210-52 |
| | |
| | 7)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE/ISLAND AS GFI/GFI |
| | PROTECTED. PER 210-8-A-6 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 659-8096 ETX 8372 |