Plan Review Notes
Plan Review Notes For Permit 00120087
Permit Number 00120087
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PER F.A.C. ALL PLANS THAT ARE
 SIGNED AND SEALED BY AN ARCH OR ENGINEER
 MUST HAVE THE RAISED SEAL CLEARLY
 VISIBLE. ALSO ALL PLANS THAT ARE SIGNED
 AND SEALED MUST CONTAIN A TITLE BLOCK
 OF THE ARCH OR ENGINEER OF RECORD.
 PLEASE SEE F.A.C 61G15-23.002 AND 61G16
 ALSO CHAPTERS 481.221 AND 471.025
  
 2)NOTE: PLEASE SHOW COLD WATER PIPE AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 PER 250-5O OR CLRIFY IF CPVC.
  
 3)NOTE: PLEASE SEE RISER DIAGRAM. PANEL
 IS SHOWN NEXT TO METERCAN. PLANS SHOW
 ON THE OTHER SIDE OF HOUSE. PLEASE
 CLARIFY IF PANEL IS FED UNDER GROUND
 AND IF PANEL IS MCB?
  
 4)NOTE: PLEASE NOTE PER NFPA-72 2-2.1.1-
 .1 . A SMOKE DETECTOR IS REQ`D ON EACH
 LEVEL OF DWELLING.
  
 5)NOTE: PLEASE NOTE THAT NO CATV OR
 TELEPHONE OUTLETS ARE SHOWN? IF THESE
 ITEMS ARE GOING TO BE INSTALLED ? THEN
 ALL MUST BE ON PLANS.
  
 6)NOTE: PLEASE SEE SECOND FLOOR PLAN.
 OUTLETS MISSING PER 210-52 IN BEDROOM?
 AND OUTLET PER 2` OF WALL 210-52
  
 7)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE/ISLAND AS GFI/GFI
 PROTECTED. PER 210-8-A-6
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 ETX 8372