| 2001-03-12 00:00:00 | CHECKLIST: |
| | 1-PROVIDE CURRENT SBCCI OR DADE COUNTY |
| | PRODUCT APPROVAL FOR: |
| | -GARAGE DOOR WITH THE MINIMUM DESIGN |
| | PRESSURES AS CALCULATED BY THE |
| | ENGINEER OF RECORD. |
| | -DOUBLE DOORS W/ TRANSOM ABOVE ASSEMBLY |
| | AS SHOWN ON EXTERIOR FRONT ELEVATION. |
| | -SLIDING GLASS DOORS (EXPIRED). |
| | 2-CLARIFY WHY SURVEY DOESN'T SHOW THE |
| | DRIVEWAY. PERMIT FOR DRIVEWAY CANNOT |
| | BE ISSUED IF IT'S NOT SHOWN. |
| | 3-PROVIDE COMPLETE SET OF ENGINEERED |
| | DRAWINGS FOR " ROYAL WALL" PANELS |
| | SHOWING ALL REINFORCING. |
| | -ENGINEER OF RECORD TO REVIEW THESE |
| | SHOP DWGS PRIOR TO SUBMITTAL. |
| | 4-ENERGY CALCULATIONS: |
| | -ENERGY CALCULATIONS NEED TO BE DONE |
| | ACCORDING TO THE ROYAL WALL SYSTEM. |
| | SEE ROYAL WALL PANELS FOR INSULATION |
| | VALUES AND MATERIALS USED. |
| | 5-STORM PANELS: |
| | -PROVIDE A KEY PLAN AND COMPLETE |
| | INSTALLATION SCHEDULE. |
| | -CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE & |
| | SPACING TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | PANEL SPAN, EDGE DISTANCE, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO. |
| | -NOTE: ALL THIS INFORMATION MAY BE |
| | SUBMITTED AT A LATER DATE, BUT UNDER |
| | A SEPARATE PERMIT. |
| | 6-SOIL TEST REPORT TO HAVE ORIGINAL |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | OF FLORIDA STATUTES. |
| | 7-PAY ADDITIONAL FEES OF $1241.39 FOR |
| | LOW BUILDING VALUATION, RADON FEES AND |
| | WESTERN EXPANSION FEES. PLEASE, PAY |
| | ATTACHED RECEIPT. |