Plan Review Notes
Plan Review Notes For Permit 00120084
Permit Number 00120084
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED;
  
 1.ENERGY CAULKS ARE NOT THE SAME. TWO
 ARE FOR ABACOA AMD ONE IS FOR ANDROS
 ISLE.
  
 2.ENERGY CAULKS CALL FOR 12 SEER A/C
 UNIT A/C PLAN SHOWS 10 SEER.
  
 3.DRYER VENT CANNOT GO THRU A ZERO LOT
 LINE WALL. VENT MUST GO THRU ROOF.
  
 A/C PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8377