| Plan Review Notes For Permit 00120084 |
| Permit Number |
00120084 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT CLARIFICAITON OF | | | SERVICE.RISER SHOWS PANEL NEXT TO METER? | | | YET PLANS SHOWS PANEL AND METER ON TWO | | | SIDES OF HOUSE? | | | | | | 2)NOTE: PLEASE SUBMIT CLARIFICATION ON | | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | | COLD WATER PIPE? PER 250-50. IS CWP CPVC | | | | | | 3)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | | MAINS/PANELS/ BRKRS. ALL MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER NEC | | | 110-9. | | | | | | 4)NOTE: PLEASE SEE OCP FOR HOT WATER | | | HEATER. NOTE 20A BRKR? 125% 422-13 | | | | | | 5)NOTE: AS PER 61G15-23.002 OF THE F.A.C | | | ALL PLANS CONTAINING SEAL MUST CONTAIN | | | A TITLE BLOCK OF THAT PERSON OF RECORD. | | | ALSO PER CHAPTER 471.025 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FORREVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|