Plan Review Notes
Plan Review Notes For Permit 00120084
Permit Number 00120084
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT CLARIFICAITON OF
 SERVICE.RISER SHOWS PANEL NEXT TO METER?
 YET PLANS SHOWS PANEL AND METER ON TWO
 SIDES OF HOUSE?
  
 2)NOTE: PLEASE SUBMIT CLARIFICATION ON
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 COLD WATER PIPE? PER 250-50. IS CWP CPVC
  
 3)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 MAINS/PANELS/ BRKRS. ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER NEC
 110-9.
  
 4)NOTE: PLEASE SEE OCP FOR HOT WATER
 HEATER. NOTE 20A BRKR? 125% 422-13
  
 5)NOTE: AS PER 61G15-23.002 OF THE F.A.C
 ALL PLANS CONTAINING SEAL MUST CONTAIN
 A TITLE BLOCK OF THAT PERSON OF RECORD.
 ALSO PER CHAPTER 471.025
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FORREVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372