| Plan Review Notes For Permit 00120065 |
| Permit Number |
00120065 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE ALARM SYSTEM TO BE CLASS A OR | | | FULLY ADDRESSABLE. | | | 2) SMOKE DETECTOR REQUIRED ABOVE FIRE | | | ALARM CONTROL PANEL. | | | 3) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | | TO BE AUDIBLE THROUGHOUT THE BUILDING. | | | 4) FIRE ALARM SYSTEM IS TO BE MONITORED | | | BY A LICENSED UL LISTED CENTRAL STATION. | | | 5) SMOKE DETECTORS TO BE A MINIMUM OF | | | THREE FEET FROM AIR CONDITIONER | | | DIFFUSERS. | | | 6) FIRE ALARM SYSTEM TO BE TESTED WITH | | | FIRE RESCUE DEPARTMENT WHEN COMPLETED. | | | | | | APPROVED PROVISO: | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|