| 2001-05-24 00:00:00 | SUBMITTAL CHECKLIST: |
| | |
| | 1-PROVIDE CURRENT DADE COUNTY OR SBCCI |
| | PRODUCT APPROVAL FOR: |
| | - SLIDING GLASS DOORS FOR THE SIZES |
| | SHOWN ON PLANS. INFORMATION SUBMITTED |
| | IS ONLY FOR TESTING OF THAT SPECIFIC |
| | UNIT. (SEC 1707.4 CITY AMENDMENTS TO |
| | SBC 1997. SEE ATTACHED COPY). |
| | NOTE: IN ORDER TO EXPEDITE THE REVIEW |
| | PROCESS, MAKE SURE THAT PRODUCT |
| | APPROVAL TO BE SUBMITTED WILL MEET THE |
| | DESIGN PRESSURES CALCULATED BY THE |
| | ENGINEER OF RECORD AND THAT THE |
| | STRUCTURAL BUCK DETAIL IS ADEQUATE. |
| | 2-PROVIDE COMPLETE INFORMATION FOR |
| | STORM PANELS UNDER A SEPARATE PERMIT. |
| | THIS ITEM WAS REQUESTED ON PROVISO |
| | DATED 3-5-01 AND IS NOT DONE YET. |
| | 3-ROYAL WALL ENGINEERED DRAWINGS: |
| | A)ENGINEER NEED TO SIGN, SEAL AND DATE |
| | EACH SHEET AS REQUIRED BY CHAPTER 471 |
| | OF FLORIDA STATUTES. |
| | B)ENGINEER NEEDS TO PROVIDE ALL HIS |
| | INFORMATION AS REQUIRED BY CHAPTER |
| | 471 OF FLORIDA STATUTES. |
| | C)ENGINEER OF RECORD FOR THE STRUCTURE |
| | TO REVIEW ALL ENGINEERED ROYAL WALL |
| | DRAWINGS PRIOR TO SUBMITTAL TO THIS |
| | OFFICE. |
| | D)PROVIDE TWO COPIES OF EVERY DOCUMENT |
| | SUBMITTED. ONE GOES TO THE FIELD AND |
| | THE OTHER ONE GOES TO THE PUBLIC |
| | RECORDS FILE. |
| | E)ROYAL WALL ENGINEER DIDN'T SIGN, SEAL |
| | AND DATE DRAWINGS SD1 AND SD2. |
| | |
| | NOTES: |
| | -STAMPED DOCUMENTS ARE THE ONES THAT ARE |
| | APPROVED. INSERT THEM IN THE FIELD SET. |
| | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL |