Plan Review Notes
Plan Review Notes For Permit 00111379
Permit Number 00111379
Review Stop R
Sequence Number 2
Notes
Date Text
2001-03-05 00:00:00APPROVED WITH PROVISO:
  
 1-BEFORE INSTALLATION, PROVIDE PRODUCT
 APPROVAL FOR THE FOLLOWING:
 -FLAT ROOF SYSTEM TO BE USED. WHAT WAS
 SUBMITTED WAS THE SPECS NOT THE ACTUAL
 PRODUCT APPROVAL.
 -SLIDING GLASS DOORS PRODUCT APPROVAL
 IS EXPIRED AND THE DESIGN PRESSURES
 OF THESE DOORS DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD OF THIS HOUSE.
 -ROUND AND FIXED WINDOWS. NOTE: SEE
 SIZES SHOWN ON PLANS TO GET THE RIGHT
 PRODUCT APPROVAL.
 -GARAGE DOOR PRODUCT APPROVAL WITH THE
 DESIGN PRESSURES THAT MEETS THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER
 OF RECORD OF THIS HOUSE.
  
 2-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
  
 3-SOIL TEST REPORT NEEDS TO HAVE
 ENGINEER'S ORIGINAL SIGNATURE AS PER
 CHAPTER 471 OF FL. STATUTES.
  
 4-PROVIDE COMPLETE SET OF ENGINEERED
 DRAWINGS SHOWING EACH PANEL
 REINFORCEMENT AND SPECS.
 SIGNED, SEALED DATED AND WITH THE
 ENGINEER'S INFORMATION AS REQUIRED
 BY CHAPTER 471 OF FL. STATUTES.
  
 5-ENGINEER OF RECORD TO REVISE THE
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM. THE VELOCITY PRESSURE
 AND THE MEAN ROOF HEIGHT DO NOT MATCH.
 SEE TABLE 1606.2A OF SBC 1997.
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.