| Plan Review Notes For Permit 00111379 |
| Permit Number |
00111379 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT. ALL MAINS/PANELS MUST | | | BE RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9/110-10 | | | | | | 2)NOTE: PLEASE SUBMIT CLARIFICATION FOR | | | GROUNDING ELECTRODE CONDUCTOE. MUST BE | | | SHOWN TO COLD WATER PIPE PER 250-50. | | | (IF NOT CPVC.) | | | | | | PLEASE SUBM,IT THE ABOVE INFORMATIO FOR | | | REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | X | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 8372 |
|